Refer to the electrical diagram in the manual of your SICCOM product (manuals available HERE)
Disconnect all power supply during the installation.
We strongly recommend, if the product is equipped with one, to install the alarm (NC contact).
- Electrical connection without alarm: Take the power cable to the terminal block of the air conditioning indoor unit. Connect the "phase” wire of the pump to the "phase” terminal of the terminal block, the "neutral” wire of the pump to the "neutral” terminal of the terminal block, and the "ground” wire (if applicable) of the pump to the "ground”
- Electrical connection with alarm: Take the power and alarm cables to the terminal block of the air conditioning indoor unit.
Connect together (using a Wago-type terminal):
– the "phase” wire from the outdoor unit
– the "phase” wire from the pump supply
– the "common” wire from the pump alarm
Connect the "neutral” wire from the pump supply to the "neutral” terminal of the indoor unit.
Connect the "NC” wire of the pump alarm to the "phase” terminal of the indoor power supply
Connect the "ground” wire (if applicable) of the pump power supply to the "ground” terminal of the indoor unit
Cut and insulate the unused "NO” wire (if applicable).